EPA 608 technician certification test: Type III: low-pressure appliances practice

48 practice questions on Type III: low-pressure appliances for the EPA 608 technician certification test. Each answer comes with an explanation and the official source.

Covers low-pressure centrifugal chillers, purge unit operation, hydrostatic rupture disks, vapor vs. liquid recovery, and vacuum requirements.

or practice the whole test

Sample questions

What is the liquid phase saturation pressure threshold at 104 degrees Fahrenheit that defines a low-pressure appliance?
  1. Below 50 psia
  2. Above 45 psia
  3. Below 45 psia (correct answer)
  4. Above 50 psia

Low-pressure appliances are defined as appliances that use a refrigerant with a liquid phase saturation pressure below 45 psia at 104 degrees Fahrenheit.

40 CFR Part 82, Subpart F: Recycling and Emissions Reduction (eCFR), Current text, retrieved November 16, 2026, 40 CFR Part 82, Subpart F: Type III: low-pressure appliances, part 1
Low-pressure appliance means an appliance that uses a refrigerant with a liquid phase saturation pressure below 45 psia at 104 °F.
What percentage of refrigerant must be recovered when using recovery equipment manufactured before November 15, 1993, before opening or disposing of a small appliance?
  1. 80 percent (correct answer)
  2. 100 percent
  3. 70 percent
  4. 90 percent

When using recovery equipment manufactured before November 15, 1993, a technician must recover 80 percent of the refrigerant in the small appliance.

40 CFR Part 82, Subpart F: Recycling and Emissions Reduction (eCFR), Current text, retrieved November 16, 2026, 40 CFR Part 82, Subpart F: Type III: low-pressure appliances, part 1
(1) When using recovery equipment manufactured before November 15, 1993, recover 80 percent of the refrigerant in the small appliance; or
What is the required percentage of refrigerant to be recovered from a small appliance with a functioning compressor when using recovery equipment manufactured on or after November 15, 1993?
  1. 85 percent
  2. 95 percent
  3. 80 percent
  4. 90 percent (correct answer)

When using recovery equipment manufactured on or after November 15, 1993, technicians must recover 90 percent of the refrigerant when the compressor in the appliance is functioning.

40 CFR Part 82, Subpart F: Recycling and Emissions Reduction (eCFR), Current text, retrieved November 16, 2026, 40 CFR Part 82, Subpart F: Type III: low-pressure appliances, part 1
(2) When using recovery equipment manufactured on or after November 15, 1993, recover 90 percent of the refrigerant in the appliance when the compressor in the appliance is functioning, or 80 percent of the refrigerant in the appliance when the compressor in the appliance is not functioning; or
What is the maximum full charge weight allowed for an appliance to use system-dependent equipment, unless the equipment is permanently attached as a pump-out unit?
  1. 20 pounds
  2. 15 pounds (correct answer)
  3. 50 pounds
  4. 10 pounds

System-dependent equipment may not be used with appliances having a full charge of more than 15 pounds of refrigerant unless it is permanently attached as a pump-out unit.

40 CFR Part 82, Subpart F: Recycling and Emissions Reduction (eCFR), Current text, retrieved November 16, 2026, 40 CFR Part 82, Subpart F: Type III: low-pressure appliances, part 1
System-dependent equipment may not be used with appliances with a full charge of more than 15 pounds of refrigerant, unless the system-dependent equipment is permanently attached to the appliance as a pump-out unit.
What is the maximum annual leak rate allowed for industrial process refrigeration equipment normally containing more than 50 pounds of refrigerant before repairs must be made?
  1. 15 percent
  2. 35 percent (correct answer)
  3. 20 percent
  4. 50 percent

Owners or operators of industrial process refrigeration equipment normally containing more than 50 pounds of refrigerant must have leaks repaired if the appliance is leaking at a rate such that the loss of refrigerant will exceed 35 percent of the total charge during a 12-month period.

40 CFR Part 82, Subpart F: Recycling and Emissions Reduction (eCFR), Current text, retrieved November 16, 2026, 40 CFR Part 82, Subpart F: Type III: low-pressure appliances, part 2
The owners or operators of industrial process refrigeration equipment normally containing more than 50 pounds of refrigerant must have leaks repaired if the appliance is leaking at a rate such that the loss of refrigerant will exceed 35 percent of the total charge during a 12-month period in accordance with paragraph (i)(9) of this section, except as described in paragraphs (i)(6), (i)(7) and (i)(10) of this section, and paragraphs (i)(2)(i) and (i)(2)(ii) of this section.

Other topics on this test

Sources

Tests are given by EPA-approved certifying programs, not by EPA itself. EPA does not issue certification cards. ExamVerdict is not affiliated with US Environmental Protection Agency (EPA), given by EPA-approved certifying programs. Check the official material before test day.